Falcon SG2K-1T-HW Manuale Utente

Pagina di 26
SG Series
TM
UPS PLUS
®
2kVA & 3kVA 
24
 
Electrical Input  
Nominal AC Voltage  
120V 
230V 
120V 
230V 
230V 
AC Voltage Range  
87 – 140V 
170 – 275V 
87 – 140V 
170 – 275V 
170 – 275V 
Current – Amps  
14.2 
7.4 
21.4 
11.2 
7.5 
11.3 
Frequency  
50/60 Hz  ± 5% (Auto  – Tracking)  
Power Factor Correction  
> 0.95 
Efficiency  (Typical)  
> 86% 
> 85% 
 
Electrical Output  
Watts 
1400 
2100 
1400 
2100 
AC Voltage  
(Switchable) 
100V 
110V 
115V 
120V 
200V 
220V 
230V 
240V 
100V 
110V 
115V 
120V 
200V 
220V 
230V 
240V 
120V 
1
(700W 
split-
phase, 
each
 
5-20R)
 
208V 
220V 
230V 
240V 
120V 
2
1050W 
split-
phase, 
each  
5-20R) 
208V 
220V 
230V 
240V 
Frequency  
50/60 Hz (Auto Tracking ) 
Frequency Stabi lity 
± 0.3% (Battery Mode)  
Voltage Regulation  
± 2% 
± 5% 
± 3% 
Step Load Change  
± 7% for 100% load variation  
Harmonic Distortion  
< 3% Linear Load, < 5% Non -Linear Load  
Overload  
105% load for 50 Seconds  
Crest Ratio  
3:1 
 
Battery 
DC Voltage  
72V 
96V 
Type 
12V, 7AH Sealed  Lead Acid  Maintenance -Free 
Back Up Time                  @ Full Load  
                                       @ 1/2  Load  
7 Minutes  
20 Minutes  
5.5 Minutes  
15 Minutes  
7 Minutes  
20 Minutes  
5.5 Minutes  
15 Minutes  
Recharge Time  
8 Hours to 90%  
Battery times are approximate.  
 
Transfer Time  
Line Fails/Recovers  
Zero 
UPS to Bypass or Reverse  
< 4ms 
After Overload  
Auto Transfer to UPS  
 
Electrical Connections  
Input                                 - T Models  
 
6’ Cord with   
5-20P 
6’ Cord with  
6-20P, L6 -20P 
or Schuko  
6’ Cord with  
L5-30P 
6’ Cord with  
6-20P, L6 -20P 
or Schuko  
6’ Cord with 6 -20P, L6 -20P 
or Schuko  
 
                                       -HW Models  
Hardwire  
Hardwire Not Available  
Output                              -T Models  
 
 
(6) 5-15R or 
(3) 5-15R & 
(2) 5-20R 
(6) IEC 320  
or (1) L6 -20R 
(6) 5-15R or 
(3) 5-15R & 
(2) 5-20R 
(6) IEC 320  
 or (1) L6 -20R 
(2) 5-20R & (1) L6 -20R 
 
-HW Models  
Hardwire  
Hardwire Not Available  
Contact the factory for  other input/output options.  
 
Environmental  
Operating Temper ature 
0º C - 40º C (32º F to 104º F)  
Humidity 
10% to 95% Non  – Condensing  
Altitude  
7,000 Feet   
Cooling 
Low Velocity Forced Air Fans  
Audible Noise @ 1 Meter  
<50dBA 
 
Controls and Indicators  
LED 
Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest , Battery  & Load Capacity Level  
Audible Alarms  
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency,  High Temp. , Over Load, Fault Alarm  
Communications  
RS-232 Serial Port    (Bundled UPSilon 2000 Software)  
 
Mechanical  
Dimensions H x W x D  inch es (mm) 
13.8 x 7.6 x 18.9      (350 x 193 x 480)  
13.8 x 7.6 x 30 .0     (350 x 193 x 720)  
Weight                                      lb. (kg)  
68.4   (31)  
81.4   (37)  
150.0   (68) 
Agency Listing  
-1T Models: UL 1778, CUL, FCC Class A     -HW Models:  UL 1778 &  CUL pending  
-2T Models  (except  –HW models) : UL 1778, CUL, CE 
available with Schuko plug only
 
 
Available Options  
Option A  
60 Hz to 50 Hz  Frequency  Conversion  
Option B  
50 Hz to 60 Hz  Frequency  Conversion  
Option C  
SNMP/HTTP Network Card (Internal)  
Option D 
Standard Contact Closure Interface Card  
Maintenance Bypass  
Make-Before-Break External Wrap Around   
External Battery Packs  
Extended Run Time Battery Packs (minutes to hours)  
Fast Battery Charger  
Fast Charger internal to the Extended Battery Pack Cabin et (Required for battery times 2 hours or more.)  
 
 Model Number  
SG2K-1T 
SG2K-1T-HW 
SG2K-2T 
SG2K-2T-HW 
SG3K-1T 
SG3K-1T-HW 
SG3K-2T 
SG3K-2T-HW 
SG2K-2TX 
SG2K-2TXI
1
 
SG3K-2TX 
SG3K-2TXI
2
 
Nominal VA  
2000 
3000 
2000 
3000