Falcon XG3K-1T Manuale Utente

Pagina di 32
 
 
17
TURNING THE UPS OFF  
To turn off the UPS: 
While in Normal On-line mode, press the BYPASS button for one second. The UPS will go into 
BYPASS MODE. Next, turn off the INPUT BREAKER. The unit will shut down immediately. 
 
 
 
 
  NOTE! 
 DURING SHUT DOWN, DO NOT PRESS ANY BUTTON SINCE UPS MIGHT BE RE-
ENERGIZED AND DELIVER POWER TO ITS OUTPUT UNEXPECTEDLY. 
 
 
6.0 UPS SETUP CONFIGURATION
 
 
This section describes how to reconfigure the internal UPS setup options, by entering the 
CONFIGURATION MODE. The setup parameters includes: UPS output voltage & enable or 
disable GREEN MODE. 
 
 
 CAUTION                                
 
 
Never change the voltage settings when the UPS is ON and powering any connected loads. 
 
 
   NOTE! 
 Setting the UPS output voltage to 100 VAC will derate the UPS output VA and 
WATTAGE ratings. Please refer to the SPECIFICATIONS located at the end of 
this manual for information on your specific UPS model.
 
 
How To Place The UPS Into Setup/CONFIGURATION Mode 
 
To put the UPS into configuration mode, press the “FUNTION/TEST” and “SET/ALARM 
SILENCE” buttons at same time and hold them for one
 
second. The unit will emit one audible 
beep and then enter CONFIGURATION MODE.  
 
 
Note that on the display panel, you will see a single row, 8 
BIT column located at the bottom of the display. The most 
right bit is function “BIT 0”, the far left is status “BIT 7”. 
Note that there is an illuminated dot “.” in BIT 0 when the 
unit is in CONFIGURATION MODE.  
Pressing the “FUNCTION/TEST” button will move the dot 
from function BIT 0 to function BIT 6. When selecting 
function BIT 0 through BIT 6, observe whether status BIT 
7 is selected (dot) or deselected (no dot,) for the function 
bit selected. To select (dot) or deselect (no dot) the 
function you are presently in, press the “SET/ALARM 
SLIENCE” button to set or deselect function BIT 7.  Press  
the “SET/ALARM SLIENCE” and  FUNCTION/TEST” 
buttons at same  time again and hold for one second. The 
alarm buzzer will sound one short beep to acknowledge  
 
 
 
 
 
 
 
 
 
 
 
 
 
the  UPS  has stored the settings.      
 
 
GREEN MODE (Function BIT 3) 
 
BIT 7
BIT 0 
 
BIT 7