9.0 TROUBLESHOOTING 
 
The XG Series UPS has an audible alarm feature to alert the user of potential problems. Please 
use following information to determine and resolve alarms and conditions. 
 
The XG Series UPS notifies the user of abnormal conditions via audible alarms.  The alarms 
are as follows: 
 
Alarm and Possible Cause 
Solution 
Three short beeps, continuously 
•  Utility voltage out of range 
•  The UPS is in Battery Mode 
Check the input voltage 
Four short beeps, continuously 
•  Utility Frequency out of range 
•  The UPS is in Battery Mode, 
remove the input power and 
check the input frequency 
Five short beeps, continuously 
•  UPS internal over temperature 
•  The Fan is not turning 
•  Check the ventilation and 
remove any blockage 
•  Call  Falcon Service for a fan 
replacement 
Six short beeps, continuously 
•  PFC over current protection in 
action 
 
•  Verify the input AC voltage is 
not too low, remove some 
load from UPS output 
Seven short beeps, followed by 
three long beeps, every five seconds
•  Battery low after utility loss 
•  Save the data, turn off the 
equipment and wait for utility 
power to return 
One long beep every few seconds 
•  Output overload 
•  Charger Fail 
•  UPS Alarm, continuous 
 
Check the LCD display 
 
•  Remove some load 
•  Call Falcon Service 
•  Call Falcon Service 
 
 
TROUBLESHOOTING GUIDE 
Check the UPS input voltage, input plug and wiring first. Then prepare the serial number and 
model number of the unit for Falcon Service if the problem cannot be solved.  
Problem and Possible Cause 
Solution 
UPS will not turn on 
•  Input breaker not switched ON  
•  UPS input breaker tripped 
•  Input/battery cables not  
correctly fitted 
 
 
 
 
•  Verify the UPS Input breaker 
on front panel is turned ON 
•  Verify the connected load is 
less than the rating of the UPS 
•  Verify the input cable and 
battery is connected to the 
UPS and battery module. 
Verify the battery circuit is 
turned ON