ADCP-80-524 • Issue 1 • November 2001
Page 17
©
 2001, ADC Telecommunications, Inc.
mounting
 brackets allow mounting with WECO 1.00-inch (2.54 cm) hole spacing or EIA 1.25-
inch
  (3.18  cm)  hole  spacing.  The  slotted  mounting  hole  pattern  in  the  mounting  brackets
compensates
 for vertical rack differences and allows mounting the fuse panel in either 1.75- or
2-inch
 (4.45 or 5.08 cm) rack spaces.
1.23 Environmental Characteristics
The
 environmental characteristics of the PowerWorx Type 70 Series Power Distribution Fuse
Panel
 are listed in 
.
 
2
ACCESSORIES
The
 following accessories for the PowerWorx Type 70 fuse panel are available:
• Standard
 Type 70 fuses with current capacity of from 0.2 Amp to 10.0 Amps
• Cable
 management bar with mounting screws. Provides cable tie points. Installed at rear
of
 fuse panel by fastening ends of bar to both sides of the panel
• Four
  sizes  of  two-hole  compression  lugs  for  #2,  #4,  #6,  and  #14  AWG  wire  for  input
power
 connection
• Kit
 of perforated fuse value designation cards and plastic covers 
• Kit
 of fused equipment designation cards, a card holder, and a plastic cover
Table 1. PowerWorx Type 70 Fuse Panel Environmental Characteristics
PARAMETER
DESCRIPTION
Operating
 temperature
–5°
 C to +50° C
Storage
 temperature
–45°
 C to +85° C
Humidity
 range
0%
 to 95% humidity (non-condensing)
Altitude
 range
–197
 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
Fire
 rating
All
 components UL94-V1 or better
Acoustic
 noise
0
 dBA above ambient
Heat
 dissipation (fully loaded 
traditional
 panel)
40
 watts maximum@ 65 A per bus, 80 watts maximum @ 130 A 
total
 fuse panel load
Heat
 dissipation (no load)
1
 watt per bus