American Power Conversion 20-30 kVA 480V Manuale Utente

Pagina di 4
990-2870B
07/2006
*990-2870B*
APC Smart-UPS
®
 VT ISX Enclosure
20-30 kVA 480V for 5 Battery Modules and 
with Power Distribution Unit and 
Isolation Transformer
Installation
IMPORTANT SAFETY INSTRUCTIONS 
SAVE THESE INSTRUCTIONS
LOAD ON
LOAD ON
ON-BA
ON-BATTTT
BYPASS
ASS
FAUL
AULT
ESC
ESC
?
Warning
Always read the separate Safety Sheet 990-2822 prior to the 
installation.
Warning
All electrical power and power control wiring must be installed by 
a qualified electrician, and must comply with local and national 
regulations for maximum power rating
.
Warning
The UPS must be supplied from a: 208Y/120V or 220Y/127V 4W+ 
GND 60 Hz source.
Note
Power terminal lug diameter: minimum 6 mm. 
Torque value: 62 lbf
.
in/7 Nm.
1
Cable Entry
Cable entry takes place from the rear of the UPS. Pull out the lower end of 
the handle and turn it counterclockwise to a horizontal position to open 
the door.
Preparing for cabling (general)
Use a torx screwdriver to loosen the four M4 screws from the cable 
landing cover and remove.
Preparing for bottom and top entry
Use a hammer to 
punch out 
knockouts and line 
holes with 
grommets (not 
supplied).
Note
Make sure that the UPS is in its location of use before you 
start the cabling.
Cable landing area 
for AC input 
Power Distribution 
Unit (PDU)
Conduit box 
Power module with 
cable landings for 
battery cables and
communication
cables
Smart-UPS® VT ISX w/transformer and PDU, 20-30 kVA, 480 V, Installation 
Preparing for top cable entry
From the rear of the inside of the UPS push the top cover
 
spring locks
 
backwards to lift up the rear end of the top cover. 
Slide out the top cover (mind the wing on either side of the plate).
Punch holes in labeled area between the two rails on the rear of the 
top cover for conduits as required. Line hole(s) with grommets (not 
supplied). Reinstall the top plate.
2
AC and Ground Cable 
Landings
Bottom cable entry
Feed the input cables 
in conduits (not 
supplied) through the 
punched holes in the 
bottom plate. 
Use cable ties to 
attach the cables to 
the slotted plate.
Connect the input 
cables (L1, L2, L3), 
to the cable landings.
Connect the ground cable using the provided screw (earth symbol 
beneath the applicable screw).
Reinstall bottom cable landing cover.
Rear 
L1
L2
L3