Connect  the  supplied  battery  module  cable  from  extended 
battery module to the external battery port of the rear of UPS.
If continuing to add up extended battery module, repeat above 
steps.
5.3
Emergency Power Off (EPO) set up
PROTECT  B.  1500,  2000  and  3000  include  EPO  port  that 
allows  power  to  be  shut  down  the  protected  equipment 
immediately and does not follow the shutdown procedure from 
any power management software.
i
Note: 
After pressing the EPO all outputs of the UPS are 
without power. For restarting the system you have 
to  quit  /  reset  the  EPO  and  manually  restart  the 
UPS by pressing the on / off button.
Follow the procedure to install the EPO switch as below.
1.
Check the UPS is turned off.
2.
Remove the power supply from the EPO cradle 
on  the  rear  of  the  UPS  by  loosening  the  two 
outer screws. 
3.
Connect  isolated,  normally-open,  dry  contacts 
(rated  to  handle  60Vdc  maximum,  30Vac  RMS 
maximum,  and  20mA  maximum)  across  the 
EPO device to Pin 1 and Pin 2.  
4.
Use  non-shield  wiring,  size  0,3  mm²  -  0.75 
mm². Plug the connector into the socket and fix 
it by screwing the two outer screws tight. 
5.
Verify that the externally-connected EPO switch 
is  not  activated  to  enable  power  to  the  UPS 
output receptacles.
6.
Plug  in  the  UPS,  then  pressing  power  switch     
button to turn on the UPS.