AEG 10000 Manuale Utente

Pagina di 58
13 
Overload behaviour 
up to 105 % continuous; 
in battery mode 
> 105 % for 10 s  
 
Short circuit behaviour 
3 x I
N
 for 300 ms 
Battery 
Autonomy time (full load with internal battery)   
PROTECT C. 6000 
8 min. 
PROTECT C. 10000 
5 min. 
Autonomy times with external optional battery expansions  
(only for PROTECT C. models): 
Autonomy times (full load) 
Coupled 
battery modules 
C.6000 C. 
10000 
25 min. 
15 min. 
45 min. 
25 min. 
60 min. 
33 min. 
 
Rated direct voltage (intermediate circuit) 
 
PROTECT C. 6000 (S) 
240 Vdc 
PROTECT C.
 
10000 (S) 
240 Vdc 
Battery charging current 
PROTECT C. 6000 
2.0 A 
PROTECT C. 6000 S 
4.2 A 
PROTECT C.
 
10000 2.0 
PROTECT C.
 
10000 S 
4.2 A 
 
Recharge time 
~ 7 h (UPS with internal  
to 90% of rated capacity  
battery only) 
(PROTECT C. – models) 
~ 11 
 
h (with 1 battery
 expansion) 
 
~ 16 h (with 2 battery 
 expansions) 
 
~ 24 h (with 3 battery 
 expansions)