61175044L2-22B
AC/DC POWER SUPPLY AND BATTERY CHARGER
JOBAid, 61175044L2-22B, December 2002
Technical Support 1-888-4ADTRAN (1-888-423-8726)
Copyright 
 2002 ADTRAN, All Rights Reserved
MOUNTING INSTRUCTIONS
Remove the Total Access 750/850 AC/DC Power Supply 
(ADTRAN P/N 1175043Lx) from the box and inspect for 
damage. If damage is apparent, contact your carrier or 
supplier.
Place the power supply with the power cord oriented 
downward.
Use four #6 x 3/8" machine screws (supplied) to mount the 
power supply to either side of the Total Access 750/850 shelf.
Note: Threaded mounting holes are provided on both sides of 
the shelf.
Note: For battery backup installations, it is recommended to 
mount the power supply on the left side of the Total 
Access 750/850 shelf, next to the battery cover hinge.
Note: Alternatively, the power supply can be mounted to the 
backboard with four #6 x 1" wood screws (not supplied).
The device complies with Part 15 of the FCC rules. Operation is 
subject to the following two conditions: (1) This device may not 
cause harmful interference, and (2) this device must accept any 
interference received, including interference that may cause 
undesired operation.
Changes or modifications not expressly approved by ADTRAN
could void the user's authority to operate this equipment.
WARRANTY
Warranty for Carrier Network products manufactured by 
ADTRAN and supplied under Buyer's order for use in the U.S. is 
ten (10) years. For a complete copy of ADTRAN's U.S. Carrier 
Networks Equipment Warranty: (877) 457-5007, Document 414.
STATUS LEDS
RELAYS
Alarm Relay
Provided for customer use
Battery Disconnect Relay
Disconnects battery pack from the system if the battery voltage falls below -40 VDC
Prevents damage to batteries
CIRCUIT BREAKER
 
3- amp circuit breaker
 Protects 
unit 
from 
over 
current
 
Rocker button extends out from front panel when tripped
 
Reset by pushing in on the rocker button
GROUNDING
An 18 AWG or larger ground wire is required to connect additional ground connector to "ground
bus" in customer equipment room.
ELECTRICAL SPECIFICATIONS
TELECOMMUNICATIONS CODES
AC Power Operation (AC power only)
Battery Operation (AC power supply or battery backup)
GREEN
OK
GREEN
OK (charging)
YELLOW
Power Fail
YELLOW
Discharging
RED
Power Fail
RED
Low (<-40 V)
OFF
Power Fail
OFF
Disconnected
Condition
Alarm Relay
Normal
Open
AC Power Failure/
Battery Backup engaged
Cycles open/closed once per second if AC voltage <88 Vrms at full load and battery 
backup is connected
Battery voltage <-45V
Stays closed if voltage <-45 VDC to indicate that battery is becoming depleted
AC/DC POWER
SUPPLY AND
BATTERY CHARGER
P/N:
1175043L1
CLEI: SIMPAAAARA
P/N:
1175043L2
CLEI: SIMPAADARA
P/N:
1175043L3
CLEI: SIMPAAEARA
C A U T I O N ! 
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
Note:  The AC/DC Power Supply 
and Battery Charger is 
designed for use with the 
Total Access 750 and 850. 
It is not used with the Total 
Access 612/616/624 units.
AC input: 115 V nominal
Range: 90 to 132 VAC
DC output: -54 V, 60 W average, 100 W peak
Battery charging: 16 hr nominal, 24 hr maximum
Battery discharge: Up to 8 hours
1
2
3
Code
Input
Output
PC
F
C
TC
IC
E