MGE UPS Systems 3.5 to 21 kVA N+1 Manuale Utente

Pagina di 54
Efficiency
85% minimum, 88% typical (on-line mode); 97% typical (off-line mode) at full kVA/Watt load.
Power Factor
Rated kVA is available over a power factor range of 0.6 lagging to 0.6 leading at nominal volt-
age.  Watt rating should not be exceeded.
Total Harmonic 
Distortion
Less than 1% for linear load conditions, 3% maximum for crest factor loads up to 3:1.
Line Regulation 
System output voltage variation, less than 1% over the DC voltage range.
Load Regulation
System output voltage variation, less than 1% from zero to full load at nominal DC input.
Output Frequency
User-selectable, 50Hz or 60Hz.  Free run frequency stability shall be within +/-0.02% of the
selected frequency.
Short Circuit Current
(SCC)300% minimum of rated load current for four cycles.  A SCC is defined as a current that
exceeds 150% of rated current.
Overload Capability
Continuous overload up to 108% of rated VA/watts at 50°C maximum.
Transient Deviation 
and Recovery
Within 20% of average value for any change in output current or step change in input
voltage within specified limits.  Recovery within 1 millisecond from zero to full load. 
EMI Emission
Battery Bus less than 30dBrnc.  FCC 47 CFR part 15 class A; EN 55022 class A;
CISPR 22 class A
1.4
Mechanical Specifications
Table 1-4: S4 Receiver Cabinet Mechanical Dimensions and Weights
MODEL
7 kVA
14 kVA
21 kVA
HEIGHT (in/cm)
21 / 54
31.5 / 81
42 / 107.9
DEPTH (in/cm)
18.5 / 47.5
18.5 / 47.5
18.5 / 47.5
WIDTH (in/cm)
17 / 43.7
17 / 43.7
17 / 43.7
RECEIVER WEIGHT (lb/kg)
88 / 39.9
111 / 50.3
136 / 61.7
RECEIVER + MODULES 
182 / 82.6
299 / 135.6
418 / 189.6
WEIGHT (lb/kg)
RECEIVER SHIPPING 
100 / 45.4
123 / 55.8
148 / 67.1
WEIGHT (lb/kg)
Introduction
3.5 to 21 kVA N+1 Inverter
page 1 — 4