If the current from the PV array reaches 85 amps, the 
controller will turn off to protect the circuitry. In the event of 
a shutdown, the controller automatically resets itself after 
10 minutes (if overcurrent condition is no longer present).
Se
 for information on 
configuring this function.
Automatic PV Array Night Disconnect
When using PV Charge Control mode, the PV array is 
automatically disconnected from the battery at night to 
prevent reverse leakage of power. This eliminates the need 
for a blocking diode between the battery and the PV array. If 
thin-film or amorphous solar modules are being used, diodes 
may still be required to prevent damage from partial shading 
conditions. 
Check the documentation provided with the PV modules. 
Diversion Controller
The 
C-Series controller
 
can operate as a Diversion Controller, 
also called a shunt regulator, to manage battery charging from 
alternative energy sources such as PV, wind or hydroelectric 
generators. A diversion controller monitors battery voltage 
and, when the voltage exceeds the settings for your charge 
stage (whether bulk or float), the power is diverted from the 
source (solar, wind, or hydro generator) to a “dump” load 
which will dissipate the excess power into heat. 
When used for this purpose, the 
C-Series controller
 
varies an 
amount of battery voltage to a “dump load” in order to 
redirect the excess power generated from over-charging the 
batteries. This allows the charging source to remain under 
constant load to prevent an over-speed condition which could 
occur if the charging source is suddenly disconnected from 
the battery–as series regulators do.
Consult your dealer for recommendations on diversion load 