Equalization Charging
975-0004-01-02 Rev D
31
Manual Equalization
Manual equalization of the battery can be enabled by pressing 
the Reset Switch on the right side of the 
C-Series
 until the 
status LED indicator begins to alternate between red and 
green. This could take about 10 seconds.
The equalization process will continue until the batteries have 
been held at or above the bulk setting for two hours of 
accumulated time. Once the battery voltage has been at or 
above the bulk setting for a cumulative period of two hours, 
the 
C-Series
 will return to the float stage of the charging 
process.
During the equalization process, the status LED will alternate 
between red and green and will not provide any other 
mode/status indication. Large battery banks may need several 
equalization cycles to fully stir the electrolyte and charge the 
cells. These cycles should follow one another until the battery 
voltage reaches the upper limit for the full two hours.
Figure 2-17 Front Panel LED and Reset Switch Location
Reset 
Switch 
Access
Front Panel LED 
(flashes red/green 
during equalization)