Toshiba 1700 Series Dépliant

Pagina di 2
 
56940-000 
1700 Series UPS
 
Transformer Module Connection Guide 
 
IMPORTANT SAFETY INSTRUCTIONS 
 
SAVE THESE INSTRUCTIONS.
  
This sheet contains important instructions for Toshiba 1700 Series Transformer Modules.  
These instructions should be followed during the installation of the transformer module. 
 
  The ambient temperature range in which this unit should be operated or stored is 32°F to 104 
°
F (0°C to 40 
°
C). 
  This module should not be opened under any circumstances.  There are no user servicable parts inside.   For service 
contact your local Toshiba representative, or contact the Toshiba UPS marketing department toll-free at (800) 231-1412. 
  When adding transformer modules, be sure to use the proper model unit. 
 
 
CAUTION 
 
Misuse of this equipment could result in human injury and equipment damage.  In no event will 
Toshiba Corporation be responsible or liable for either indirect or consequential damage or 
injury that may result from the use of this equipment. 
 
Inspection/Installation 
After Unpacking: 
1)  Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all 
original packing materials for return to shipping agent.  Warranty will not apply to units damaged during shipment. 
2)  Check to see that the rated capacity and the model number specified on the nameplate conform to the order 
specifications. 
 
Installation Precautions 
This transformer module is intended for use with a Toshiba 1700 Series UPS.  Any electrical or mechanical 
modifications to this equipment, without prior written consent of Toshiba International Corporation will void all 
warranties and may void UL/CUL listing.  Unauthorized modifications also can result in personal injury, death, or 
destruction of the equipment.  
When installing this transformer module follow all installation instructions and precautions 
as listed in the 1700 Series user manual 
 
Model Number 
UF1-IO-024-6BG 
Capacity 
2400VA (1.68kW) 
Input voltage
1
 
Single phase 208/240VAC, 
selectable 
Output voltage 
Single phase 120/240VAC 
Output voltage 
regulation 
Within +/- 3%, steady state 
Rated load power 
factor 
0.7 
Rated output current 
(rms) 
9.5A @ 240V 
19A @120V 
Transformers 
Input 
Isolation 
Output 
Auto 
Mechanical Design 
Weight 
60 lbs (27.3 kg) 
Dimensions 
(in[mm])
 
6[152]H x 8[203]W x 19.7[502]D 
 
Figure 1 
Module Layout 
Note:  No more than three modules should be stacked in 
any configuration.  If the transformer module is being 
used with a system that has a second battery module at 
least one module must be placed beside the others.  
Stacking four modules could result in a tipping hazard.