True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 110/120V (user selectable) under all usage
conditions
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other
UPS types
Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 110/120V (+/-2%) values
Standard internal battery set offers 14 minutes runtime at half load (800W) and 4.5 minutes at full load (1600W)
Optional BP48V60-3UNAFTA external battery packs offer expandable battery runtime
Space saving upright tower format
Fault tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure
and requires maintenance
Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS
nominal voltage adjustment and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA 5-20P input plug (user-installable NEMA 5-15P replacement plug included)/NEMA 5-15/20R & NEMA L5-20R output receptacles
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks 
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
Single line TEL/DSL or network ethernet line surge suppression
2 year manufacturer's product warranty, $250,000 
Specifications
SYSTEM OVERVIEW
Voltage
compatibility
120V AC (110/120V)
Frequency
compatibility
50/60 Hz compatible (auto-sensing)
OUTPUT
Output VA
2200
Output watts
1600
Output nominal
voltage
120V AC (110/120V)
Output voltage
regulation
Maintains full-time sine wave output within 2% of selected nominal, less than 3% total harmonic distortion (linear load) /
5% total harmonic distortion (computer load) (Less than 5% THD on-line and on-battery)
Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity /
type
6 NEMA 5-15/20R, 1 NEMA L5-20R
Customized load
management
receptacles
2 controllable load banks support load shedding and remote reboot on demand of locked network devices (3 outlets per
load bank)
Overload
protection
Via 30A input breaker
INPUT
Maximum input
amps
16A (120V) / 17.6 (110V)
Input connection
type
NEMA 5-20P (user installable NEMA 5-15P also included)
Input cord length
10ft / 3m