Tripp Lite SU6000RT3UHV Manuale Utente

Pagina di 5
Battery recharge
rate
Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected nominal
voltage at all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 276VAC, regulating output within 2%
of selected nominal
Brownout
correction
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156VAC,
regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs
6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. SELECTABLE LCD DISPLAY:
input/output voltage, Hz, battery voltage and charge level and detailed warnings regarding all major UPS functions.
LED/LCD display panel easily rotates for viewing in rackmount or tower configurations.
Alarms
Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter
fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete
Switches
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight
(lbs)
323
Shipping weight
(kg)
145.4
Unit weight (lbs)
Power Module 43.8 lbs., Battery Pack: 139 lbs.
Unit weight (kg)
Power Module: 19.7 kg, Battery Pack: 61kg
Unit Dimensions
(HWD/in)
Power Module 5.25 x 17.5 x 26, Battery Pack 5.25 x 17.5 x 25
Unit Dimensions
(HWD/cm)
Power Module 13.3 x 44.5 x 66, Battery Pack 13.3 x 44.5 x 63.5
Material of
construction
Steel
Form factors
supported
Rack (6U)
Cooling method
Built-in cooling fan
Battery Access
User replaceable, hot swappable external battery pack
ENVIRONMENTAL
Relative Humidity
0 to 95%, non-condensing
Storage
Temperature
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Line mode BTU/hr.
(Max.)
1418
COMMUNICATIONS
Network
monitoring port
Includes 2 built-in DB9 monitoring ports (1-RS232 / 1-contact closure)
Software and
cabling included
Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Cabling
included.
SNMP compatibility
Built-in accessory slot accommodates internal SNMP / Web card and other network accessories