1.22 Specifications
 lists specifications for the circuit breaker panel. 
Table 2. Circuit Breaker Panel Specifications
PARAMETER
SPECIFICATION
REMARKS
Physical
Weight
12 pounds (5.45 kilograms)
Dimensions (HxWxD)
1.75 x 17.13 x 11.0 inches 
(44 x 435 x 280 mm)
See 
.
Color
Putty white
Rack mounting
19- or 23-inch (EIA or 
WECO hole spacing)
Flush or with a recess of 1, 2, 
3, or 4 inches (25.4, 50.8, 
76.2, or 101.6 mm)
Electrical
Operating voltages
–24 Vdc nominal 
Input range: –21 to –30 Vdc 
–48 Vdc nominal
Input range: –42 to –56 Vdc 
Input current
45 Amps max. per bus
90 Amps max. per panel
Circuit breaker rating
5 or 10 Amps
Positions are labeled
Circuit breaker positions
7 per bus
14 per panel
Max. circuit breaker size
10 Amps rating
45 Amps per bus
Input terminal type
2-hole compression lug 
Stud type accepting up to #6 
AWG wire
Output terminal type
7-position screw-down barrier 
terminal strip
Accepting a variety of wire 
up to 12 AWG wire
Alarm contact current
1 Amp max.
Grounding connection
Two #10 studs and nuts on 
0.625 centers 
Environmental
Operating temperature
–5º C to +55º C
Storage temperature
–45º C to +85º C
Humidity range
0% to 95% humidity
No condensation
Altitude range
–197 feet (0.06 km) to 13,000 
feet (3.96 km) above sea level
Acoustic noise
0 dBA above ambient
Heat dissipation (no load)
1 Watt per bus
Heat dissipation (fully loaded)
30 Watts max. at 
25º C ambient 
temperature, full load