UPS Display: User Configuration Screens
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
23
• Battery monitor test: Setting this value to True results in an automatic battery monitor test being 
performed at regular intervals specified by the Service Engineer. The three options are:
– Auto battery test - every (N) week(s).
– Auto battery test - on one day of the week.
– Auto battery test - at a specific time of the day.
• Battery capacity test: Setting this value to True results in the batteries being discharged until a 
Battery Low Voltage Level is reached. This test can only be performed manually. The test is 
used to cycle the batteries in order to calibrate the backup time with the current load and battery 
modules installed.
• Battery monitor reset: In the event of a weak battery or another battery problem, use this button 
to reset the battery monitor.