American Power Conversion Bypass Static Manuale Utente

Pagina di 56
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
39
Transfer from Online to Static Bypass 
Operation
Follow the below procedure to transfer from Online to Static Bypass Operation:
Normal
~
~
Q7
Q8
Normal
0:00 AM
Q2
UPS Summary
Normal
5.40 PM
Startup
Shutdown
Network Configuration
User Configuration
View Event Log
Predictive Maintenance
Static Bypass      Online 
Online      Static Bypass
Transfer from manual bypass to online
Transfer from online to manual bypass
Transfer from online to static bypass
Transfer from static bypass to online
Operation
Normal
Initiate transfer to static bypass             
In static bypass the load is powered directly by utility power.
There will be no UPS backup.
Normal
Normal
0:00 AM
Online to Static Bypass
Initiate transfer
Press 
Initiate transfer to Online ->
on Online to Static Bypass 
screen
Select Online -> Static Bypass 
on Operation screen
Select Operation/Configuration 
on UPS Summary screen