American Power Conversion Bypass Static Manuale Utente

Pagina di 56
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
47
Appendix A
Air Filter Exchange
Check air filters at regular intervals (every 3 months under normal working conditions) for 
accumulated dust on the surface facing the finishing panels. Change all filters at the same time.
Pull lower part of top finishing panel free of the UPS.
Lift finishing panel free of the dead front panel and remove.
Follow this procedure to remove the next finishing panel down, until all panels in one row have 
been removed. Use the same procedure for the next row of panels until all panels have been 
removed from the UPS system.