Lightwave Communications 3200 Manuale Utente

Pagina di 88
 
77
The DC power source must be: 
  electrically isolated from any AC source 
  reliably connected to earth 
  capable of providing up to 100 Watts of continuous power 
 
D.2 Overcurrent 
Protection 
 
Overcurrent protection requirements: 
  10 Amp trip 
 double 
pole 
 fast 
trip 
 DC 
rated 
 
 
  Overcurrent protection devices (e.g., circuit breakers) must be provided as part of 
each equipment rack, and are not included with the ConsoleServer. 
  The device must be located between the DC power source and the 
ConsoleServer. 
 
D.3 DC 
Supply 
Connector 
 
The supply input connectors are provided with each ConsoleServer.  However, the 
conductors are not.  See below for conductor specifications. 
 
 
Conductor 
material: 
    copper 
only 
Wire 
gauge: 
     16 
AWG 
Insulation rating: 
75°C minimum, low smoke fume, flame 
retardant 
Branch circuit cable insulation color: 
per applicable national electrical codes 
Grounding cable insulation color: 
green/yellow 
 
 
The cable type should be one of the following: 
  UL style 1028 or other UL 1581 (VW-1) compliant equivalent 
 IEEE 
383 
compliant 
 IEEE 
1202-1991 
compliant