119
PWR SPLY DC A FAIL
Power Supply DC Bus A Failed.
The primary power supply is no longer providing DC power to the control board and the touch screen.
Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and 
press RETURN on your keyboard.
PWR SPLY DC B FAIL
Power Supply DC Bus B Failed.
The secondary power supply is no longer providing DC power to the control board and CAN options.
Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and 
press RETURN on your keyboard.
PWR SPLY S1 AC FAIL
Power Supply Source 1 AC Failed.
The AC input power to the power supplies from Source 1 has failed. The power supplies are now operating on AC power 
from Source 2. The AC input from Source 1 is still good.
Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and 
press RETURN on your keyboard.