TRANSFER Menu
SR2MAN01 11/2007
69
Backup Memory 
 Module 
Transfer
Procedure for transferring the application, from the backup memory to the smart 
relay, for a 
smart relay with LCD and keyboard:
Procedure for transferring the application, from the backup memory to the smart 
relay, for a 
smart relay without LCD or keyboard:
Step Action
1
Insert the EEPROM cartridge (SR2 MEM02) with the program to be transferred into 
the slot provided.
2
Select the transfer type: 
MEMORY>ZELIO using the navigation keys    .
3
Confirm the transfer command with the 
Menu/OK key.
4
Wait for the transfer to end.
Display: 
> > > MODULE then TRANSFER. OK when it is complete.
5
Confirm again by pressing 
Menu/OK to exit the menu.
Result: the display returns to the INPUTS-OUTPUTS screen in RUN mode and to the 
MAIN menu in STOP mode.
Step Action
1
Since the smart relay 
is not powered-on, insert the EEPROM cartridge (SR2 
MEM02) into the slot provided.
2
Power up the smart relay.
During the transfer, the LED display is off.
3
Wait for the transfer to end.
During the transfer, the LED display is off, then at the end of the transfer the LED flashes.
4
z
If the flashing is slow (3 Hz), the transfer has been successful, the smart relay is in 
RUN, remove the EEPROM cartridge (SR2 MEM02).
z
If the flashing is rapid (5Hz), the transfer has failed due to incompatibility between the 
configuration necessary for the program to be transferred and that of the smart relay.
Note: When the smart relay is in STOP mode, the LED display is lit and does not 
flash.