RH Compensation
Add Min Vent sec  30
RH set point %    65
Mist shutoff %   Off
5.15.3.2 RH Compensation on Minimum Ventilation
When the humidity level reaches the RH set point + 10%, the On-Time
portion of the minimum ventilation cycle is increased by an amount
ranging from 0 to 900 seconds. Set the dipswitch #7 to ON to activate
this function.
Set the function to "18.RH Compensation" from the main menu
using the navigation buttons then press the right-arrow key. Note
that this menu only appears if the relative humidity sensor has been
enabled during the installation setup (see sec. 5.14.3).
Use the adjustment buttons to set
the time that will be added to the
minimum ventilation's On-Time
when the humidity level reaches the
Humidity Set Point + 10% 
(Add
Min Vent sec)
. Note that this menu
only appears if dipswitch #7 is
turned ON.
MAX ON TIME
ON TIME
(IN MIN. VENT.)
RELATIVE
HUMIDITY (RH)
WHEN THE HUMIDITY 
EXCEEDS THE RH SET 
POINT,  THE ON TIME 
STARTS INCREASING
RH SET POINT
NORMAL ON TIME
ON TIME +
ADDED  DELAY
ADDE
D T
IM
E
HUMIDITY COMPENSATION ON MIN. VENTILATION