Section 3 - Service and Repair
CAUTION
If frost is heavy, divert water from drain to prevent water 
from overflowing on the floor.
SPECIFICATIONS
CLR2160
COMPRESSOR/COIL SPECIFICATIONS
DANGER
DANGER
Electrocution can cause death or serious injury. Burns from 
hot or cold surfaces can cause serious injury. Take precautions 
when servicing this unit.
• Disconnect the power source.
• Do not stand in standing water when working around 
electrical appliances.
• Make sure the surfaces you touch are not hot or 
frozen.
• Do not touch a bare circuit board unless you are 
wearing an anti-static wriststrap that is grounded to 
an electrical ground or grounded water pipe.
• Handle circuit boards carefully and avoid touching 
components.
To measure the start winding resistance measure across the C and 
S pins.
To measure the run winding resistance measure across the C and R 
pins.
Also check S to R and you should get the sum of the run and start 
windings.
To ensure the windings are not shorted check the S and R to 
ground.
Figure 26. CLR2160
Water Valve
275 Ohms
Bypass Coil 
300 Ohms
Pump Motor
72 Ohms
THERMISTORS
The U-Line Model CLR2160 uses two thermistors. The 
thermistors are used in conjunction with the control panel to 
monitor the unit’s functions and troubleshooting capabilities. A 
type 1 thermistor is attached to the condenser dryer inlet and 
senses temperature after the condenser to signal length of ice-
making and harvesting time. A type 2 thermistor senses the ice 
level in the ice bin and maintains ice level in the bin.
REED SWITCH
None on this model.
EMY70HER
Voltage
115-127
Frequency
60.0
LRA
26.5
FLA
2.7
Start Winding
8.1
Run Winding
3.2
Capacitor
N/A
C
S
R
ULIN_0568_A
STARTING
RELAY
3/4" OVERLOAD 
PROTECTION