GP Series Portable Chillers 
Chapter 6: Troubleshooting 
51 of 90 
 
CC = Compressor Critical 
SC = System Critical 
PC = Process Critical  W = Warning 
Alarm Name 
Type  Possible Cause 
Solution 
Compressor Fault 
CC 
MCP Failure 
Allow the compressor to cool 
down.  If the compressor does 
not restart, disconnect power 
and verify operation of  the 
MCP internal module.  Replace 
if necessary. 
Compressor module has failed 
Discharge Pressure Sensor Failure 
Sensor Failure 
Check the wiring connection at 
the sensor, and at the controller.  
If necessary replace sensor. 
Electrical connection at 
sensor open 
Electrical connection at 
controller open 
Fan Overload 
CC 
Internal fan motor overload 
tripped 
Allow the fan to cool down.  If 
the fan does not restart when 
called upon by controller, 
replace fan motor. 
VFD Fault 
CC 
Drive has detected internal 
fault 
Locate the drive and write 
down the fault code shown on 
the display of drive.  Contact 
customer service for assistance. 
High Discharge Pressure Fault 
CC 
Dirty air cooled condenser or 
inlet filter 
Clean filter or condenser 
Dirty water cooled condenser 
or condenser valve failure 
Clean condenser or verify 
operation of condenser valve 
Condenser fan overload 
See Fan Overload Fault 
Condenser fan VFD fault 
See VFD Fault 
Ambient air or condenser 
water temperature too high 
Verify supply temperature or air 
removal capacity. 
Too much refrigerant in 
system. 
Contact Customer Service for 
assistance 
Liquid line valves closed. 
Verify operation of valve and 
wiring on controller 
Discharge pressure switch 
failure 
See Discharge Pressure Sensor 
Failure 
High Discharge Pressure Switch 
CC 
Dirty air cooled condenser or 
inlet filter 
Clean filter or condenser 
Dirty water cooled condenser 
or condenser valve failure 
Clean condenser or verify 
operation of condenser valve 
Condenser fan overload 
See Fan Overload Fault 
Condenser fan VFD fault 
See VFD Fault 
Ambient air or condenser 
water temperature too high 
Verify supply temperature or air 
removal capacity. 
Too much refrigerant in 
system. 
Contact Customer Service for 
assistance 
Liquid line valves closed 
Verify operation of valve and 
wiring on controller 
Discharge pressure switch 
failure 
See Discharge Pressure Sensor 
Failure 
High Suction Pressure Fault 
CC 
From Process fluid 
temperature too high 
Verify flow through system.  
Make corrections as necessary. 
 
CC = Compressor Critical 
SC = System Critical 
PC = Process Critical  W = Warning 
Alarm Name 
Type  Possible Cause 
Solution 
Low Discharge Pressure Fault 
CC 
Ambient air or condenser 
water temperature too low 
Verify ambient air temperature 
and air flow or condenser inlet 
water temperature.   
Too little refrigerant in 
system. 
Contact customer service for 
service call