York R134A Manuale Utente

Pagina di 140
JOHNSON CONTROLS
10
Temperatures and Flows
TEMPERATURE AND FLOWS
(English Units)
NOTES: 
1.  For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls office for application requirements.
2.  For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls office for application guidelines.
3.  The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°F)
COOLER
3
 FLOW
(GPM)
AIR ON CONDENSER (°F)
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
50 Hz
60 Hz
0600(S/P)
0157(S/P)
40
60
140
675
0
125
0590(E/V)
0157(E/V)
40
60
160
750
0
125
0650(S/P)
0177(S/P)
40
60
160
750
0
125
0630(E/V)
0177(E/V)
40
60
160
750
0
125
0720(S/P/)
0187(S/P)
40
60
160
750
0
125
0700(E/V)
0187(E/V)
40
60
160
750
0
125
0760(E/V)
0197(E/V)
40
60
180
750
0
125
0770(S/P)
0207(S/P)
40
60
180
800
0
125
0800(E/V)
0207(E/V)
40
60
180
750
0
125
0840(S/P)
0227(S/P)
40
60
180
800
0
125
0830(E/V)
0227(E/V)
40
60
180
750
0
125
0920(S/P)
0247(S/P)
40
60
180
800
0
125
0930(E/V)
0247(E/V)
40
60
180
800
0
125
1000(S/P)
0267(S/P)
40
60
180
800
0
125
1050(E/V)
0267(E/V)
40
60
250
1200
0
125
1070(S/P)
0287(S/P)
40
60
250
1200
0
125
1120(E/V)
0287(E/V)
40
60
250
1200
0
125
1180(S/P)
0307(S/P)
40
60
300
1200
0
125
1220(E/V)
0327(E/V)
40
60
300
1200
0
125
1340(S/P)
0357(S/P)
40
60
300
1200
0
125
1380(E/V)
0357(E/V)
40
60
300
1200
0
125
1500(S/P)
0397(S/P)
40
60
300
1200
0
125