York R134A Manuale Utente

Pagina di 140
JOHNSON CONTROLS
64
Dimensions – 
English
Notes:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, 
reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air patters and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance 
high pressure safety cutouts; however, the system designer MUST consider potential performance degradation. 
Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall 
- 6’; rear to wall - 6’; control panel end to wall - 4’; top - no obstructions whatsoever; distance between adjacent units - 10’. No more than 
one adjacent wall may be higher than the unit.
VIEW C-C
VIEW B-B
12"
CONTROL ENTRY
3" WIDE X 13 1/2" HIGH
1 1/2"
4"
POWER ENTRY
10" WIDE X 13" HIGH
1 3/4"
POWER ENTRY IS ON BOTTOM OF PANEL
B
 (EDGE OF UNIT
            TO COOLER
            CONNECTION)
88 1/8"
A
VIEW A-A
C
C
B
B
Models YCIV0157E/V and YCIV0157S/P
YCIV
A
B
C
D
0157E/V
19.1"
28.1"
84.5"
112.8"
0157S/P
17.4"
29.1"
90.0"
110.1"