York R134A Manuale Utente

Pagina di 140
JOHNSON CONTROLS
FORM 201.23-EG1 (1007)
7
Accessories and Options 
SOUND REDUCTION OPTIONS – The standard chiller 
has fans that operate at normal speed, no compressor 
enclosure, and is typically used in non-sensitive sound 
areas such as industrial areas or locations with loud traffic 
background noise.  One or more of the following sound re-
duction options may be employed by the system designer 
as normally generated machine noise is considered in the 
overall project design.  
Ultra Quiet Fans (Factory Mounted) – With this option, 
the basic chiller is equipped with specially designed fans 
and motors to provide lower sound levels and retain ap-
propriate  airflow.   The  result  is  reduced  fan  generated 
noise  with  no  adverse  effect  on  the  chiller  capacity  or 
efficiency performance.
Two-Speed Fans (Factory Mounted) – With this option, 
the basic chiller is equipped with fans designed with two 
operating speeds.  At high ambient conditions the fans 
operate at the normal speed with sound levels equivalent 
to Ultra Quiet Fans.  As the ambient temperature falls the 
fans automatically reduce to slow speed reducing sound 
levels.  If very low sound is required at all ambient condi-
tions normal fan speed can be inhibited.
Reduced Sound Option (Factory Mounted) – With this 
option the chiller is equipped with an unlined compres-
sor enclosure.  This option is typically used for daytime 
operation where background noise is lower than normal 
city traffic etc.
Low Sound Option (Factory Mounted) – This option 
is only available with the selection of Ultra Quiet Fans or 
Two-Speed Fans.  The chiller is equipped with an acousti-
cally lined compressor enclosure.  This option is typically 
for locations near residential areas, hotels, or hospitals 
etc where background noise is limited.  When paired with 
the Two-Speed Fan option the unit can operate at normal 
speed during the day, when background noise levels are 
noticeable, and at low speed in the evening and at night 
when background levels are lower.
SilentNight™  -  Standard  variable  speed  compressors 
result in a chiller system that has lower part load sound 
values than conventional air-cooled chillers.  Over 99% 
of chiller operating hours occur when building loads are 
less than design and/or ambient temperatures are less 
than  design.   As  a  result,  all YCIV  model  chillers  will 
operate with less than full load sound output nearly all 
the time – this is especially important on evenings and 
weekends when neighbors are home the most.  Due to 
time of day based sound regulations it may be desirable 
to  force  the  chiller  to  a  lower  sound  level  on  demand.  
The SilentNight™ control option provides a control input 
to limit sound output of the chiller based on time of day.  
This feature is programmable at the chiller panel or can 
be controlled remotely via signal (4-20mA or 0-10 VDC) 
from a BAS system.
CIRCUIT BREAKER – Power panel will come equipped 
with a factory mounted circuit breaker at point of incom-
ing  single  or  multi-point  connection  that  provides  the 
following:
•   Means to disconnect power mounted on chiller.
•   Circuit  breaker  sized  to  provide  the  motor  branch 
circuit protection, short circuit protection and ground 
fault protection for the motor branch-circuit conductors, 
the motor control apparatus and the motors.  (Chiller 
mounted circuit breaker option sized for branch circuit 
protection eliminates the need to provide a separate 
‘line of sight’ disconnect and separate branch circuit 
protection device.) 
•   Lockable operating handle that extends through power 
panel door so that power may be disconnected without 
opening any panel doors.
•   Short Circuit Withstand Rating of the chiller electrical 
enclosure when using circuit breaker option is 380, 
400, & 460V: 65,000 Amps.  Rating IAW UL508.
CONDENSER  COIL  PROTECTION  –  Standard  con-
denser coil construction materials include aluminum fins, 
copper tubes, and galvanized tube supports for generally 
good corrosion resistance. However, these materials are 
not adequate for all environments. The system designer 
can take steps to inhibit coil corrosion in harsh applica-
tions and enhance equipment life by choosing from these 
options based on project design parameters and related 
environmental factors. (
Factory Mounted)
•   PRE-COATED FIN CONDENSER COILS – The air 
cooled  condenser  coils  are  constructed  of  epoxy-
coated  aluminum  fins.  This  can  provide  corrosion 
resistance  comparable  to  copper-fin  coils  in  typical 
seashore locations. Either these or the post coated 
coils  (below),  are  recommended  for  units  being  in-
stalled at the seashore or where salt spray may hit 
the unit.
•   POST-COATED  EPOXY  DIPPED  CONDENSER 
COILS  – The  unit  is  built  with  dipped-cured  epoxy 
condenser coils. This is another choice for seashore 
and other corrosive applications (with the exception 
of strong alkalies, oxidizers and wet bromine, chlo-
rine and fluorine in concentrations greater than 100 
ppm).
•   COPPER FIN CONDENSER COILS – The unit con-
structed with copper tube condenser coils, which have 
copper  fins.  (This  is  not  recommended  for  units  in 
areas where they may be exposed to acid rain.)
PROTECTIVE CHILLER PANELS:
•   Wire Panels (full unit)
 – UV stabilized black polyvi-
nyl chloride coated, heavy gauge, welded wire mesh 
guards mounted on the exterior of the unit. Protects 
condenser coil faces and prevents unauthorized ac-
cess to refrigerant components (compressors, pipes,