System Manager/Zone Coordinator User’s Manual
21
428516-YUM-B-0908
The System Manager and Coordinator also collect samples for the last 10 changes of 
the following outputs:
RTU fan status (On/Off)
Cool1 to Cool4 (On/Off)
Heat1 to Heat3 (On/Off)
You can view this data in tabular format sorted by time and date, with the most current 
samples listed first. The data that is displayed for each sample includes:
Time and Date
Trended value
Units (if the trended value is an analog value)
The trend information is current at the time you requested the data. The System Man-
ager or Coordinator replaces old trend data with the newest data as it becomes avail-
able. The trend data cannot be printed or exported. Also, the data does not refresh 
dynamically as it is viewed.
Display Units
The user interface can display data using the English or Metric format. Table 8 shows 
the analog value units. These units apply wherever the value is displayed or modified. 
You can specify which system of units to use for the site; see Selecting Display Units 
on page 33.
Table 8: Display Units on User Interface
Type
English Units
Metric Units
No. of Decimal Places
CO
2
ppm
ppm
0
Damper Position
%
%
0
Pressure
in wc
Pa
2 for in wc
0 for Pa
Relative Humidity
%
%
0
Temperature
Deg F
Deg C
1
Time
hh:mm AM or PM
hh:mm AM or PM
n/a