Parameter copy and parameter verification
4
4.29 Parameter copy and parameter verification
4.29.1 Parameter copy
PCPY Setting
Description
0
Cancel
1
Copy the source parameters to the operation panel.
2
Write the parameters copied to the operation panel into the destination inverter.
3
Verify parameters in the inverter and operation panel. (Refer to page 398.)
REMARKS
· When the copy destination inverter is not the FR-A700 series or parameter copy write is performed after parameter copy read is
stopped, "model error (
)" is displayed.
· Refer to the
 
parameter list on page 466 and later for availability of parameter copy.
· When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy write, perform write again or
check the values by parameter verification.
· Initial settings of certain parameters are different for different capacities, so some parameter settings may be automatically
changed when parameter copy is performed from a different-capacity inverter. After performing a parameter copy from a
different-capacity inverter, check the parameter settings. (Refer to the parameter list (page 71for the parameters with different
initial settings for different capacities.)
· If parameters are copied to the inverter with additional parameters (version up model) from the inverter without additional
parameters, a value out of the setting range may be written to the inverter. In this case the inverter operates as if the initial value
is written to the parameter.
Parameter settings can be copied to multiple inverters.
Operation
1.
Connect the operation panel to the copy source inverter.
Connect it during a stop.
2.
Parameter setting mode
Press 
 to choose the parameter setting mode. (The parameter number read previously appears.)
3.
Selecting the parameter number
Turn
until "
" (parameter copy) appears. Press 
 to read the currently set value. "
" (initial value)
appears.
4.
Copying to the operation panel 
Turn 
 to change it to the setting value " ". Press 
 to copy the source parameters to the operation panel.
(" " flickers for about 30s.) 
" " and "
" flicker alternately after parameters are copied.
5.
Connect the operation panel to the copy destination inverter.
6.
After performing steps 2 and 3, turn 
 
to change it to
 
"
".
7.
Writing to the inverter
Press 
 to write the parameters copied to the operation panel to the destination inverter. ("
" flickers for about 30s.)
"
" and "
" flicker alternately after parameters are copied.
8.
After writing the parameter values to the copy destination inverter, always reset the inverter, 
e.g. switch power off once, before starting operation.
 appears...Why? 
Parameter read error. Perform operation from step 3 again.
 appears...Why? 
Parameter write error. Perform operation from step 6 again.
 and 
 flicker alternately
Appears when parameters are copied between the inverter of 
55K
 or lower and 
75K
 or higher.
1. Set "0" (initial value) in Pr. 160 User group read selection.
2. Set the following setting (initial value) in Pr. 989 Parameter copy alarm release.
3. Reset Pr. 9, Pr. 30, Pr. 51, Pr. 52, Pr. 54, Pr. 56, Pr. 57, Pr. 61, Pr. 70, Pr. 72, Pr. 80, Pr. 82, Pr. 90 to Pr. 94 , Pr. 158, 
Pr. 455, Pr. 458 to Pr. 462, Pr. 557, Pr. 859, Pr. 860, Pr. 893.
55K
 
or lower
75K
 or higher
Pr. 989 Setting
10
100