Specifications 
 
46
 
900-0112-01-00 Rev B  
Environmental Specifications 
Table 15  Environmental Specifications for All Models 
Specification Value 
Rated Temperature Range (meets all specifications) 
0°C to 50°C  
(32°F to 122°F) 
Operational Temperature Range (functions, but does not necessarily meet all specifications) 
–40°C to 60°C 
(–40°F to 140 °F ) 
Storage Temperature Range 
–40°C to 60°C 
(–40°F to 140°F ) 
Regulatory Specifications
 
 
The International Series GFX inverters are CE compliant for off-grid use.  
Grid-Interactive Use
       
 
Inverters intended for grid-interactive use must comply with established local standards which 
provide regulation for acceptable output voltage ranges, acceptable output frequency, total harmonic 
distortion (THD) and anti-islanding performance when the inverter is exporting power to a 
utility source. 
The OutBack grid-interactive models are validated through compliance testing.  The following 
specifications refer to exporting power to a simulated utility source of less than 1% voltage total 
harmonic distortion (THD). 
¾  The THD of the root mean square (RMS) current is less than 5%.   
¾  The output of the GFX inverter exceeds the minimum power factor of 0.85 with a typical power factor of 0.96 
or better.   
¾  All International Series GFX inverters are tested to comply with Table 16. 
Table 16  Interconnection Response to Voltage and Frequency 
 
 Voltage Range  
(AC Volts) 
Frequency (Hz) 
Allowed Time 
(Seconds) 
Measured Time  
(Seconds) 
V < 115 
50 
0.16 
0.020 
115 ≤ V < 202.4 
50 
2.00 
0.155 
202.4 to 253 
50 
No interruption 
No interruption 
253 < V < 276 
50 
1.00 
0.157 
V ≥ 276 
50 
0.16 
Instantaneous, but 0.137 seconds 
to zero current 
IEEE setting 
> 51 
0.16 
0.098 
IEEE setting 
< 49 
0.16 
0.102 
User setting 
> 52 
1.00 
0.605 
User setting 
< 48 
1.00 
0.656 
The acceptance ranges are selected using the system display.  The options are IEEE and USER.  The 
default setting is USER. 
¾  The IEEE option allows a range of 206 to 250 Vac at 49 to 51 Hz.  
¾  The USER option is not a fixed setting.  It follows the ac1/grid lower limit and ac1/grid upper limit settings as 
shown on the tables beginning on page 47.  The default is a range of 208 to 252 Vac at 48 to 52 Hz. 
Reconnection delay is 12 seconds after restoration of acceptable conditions.  Sell delay is one minute.  
These settings are not adjustable.