Technical specifications 
 
8.6 Thermistor motor protection 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
93
 
8.6 
Thermistor motor protection 
 
Temperature sensor   
PTC 
Thermoclick 
Evaluation characteristic to IEC 60947-8 
Type A 
— 
Summation cold resistance sensor circuit 
< 1.5 kΩ 
No-load voltage of sensor circuit 
< 30 V 
Short-circuit current sensor circuit 
< 1.2 mA 
Trip level 
3.4 … 3.8 kΩ 
Reset level 
1.5 … 1.65 kΩ 
Short-circuit detection 
< 30 Ω 
No 
Electrical isolation vis-à-vis 
Main circuit 
U
AS-i
 
U
PWR
 
Yes (U
= 400 V) 
Yes (U
= 400 V) 
Yes (U
= 400 V) 
 
8.7 
Switching frequency 
If motors are switched too often, this causes the thermal motor model to respond.  
The maximum permissible switching frequency depends on the following operating data:   
Direct and reversing starters, electronic (sDSte / sRSte) up to 4 kW 
 
3RK1315-5KS71-.AA. (0.15 A to 2 A) 
Class 10 
Device setup 
Vertical 
Horizontal 
Rated current I
e
 
2 A 
2 A 
2 A 
2 A 
2 A 
2 A 
Ambient temperature 
40 °C 
50 °C 
55 °C 
40 °C 
50 °C 
55 °C 
Degree of protection 
1)
 
2)
 
1)
 
2)
 
1)
 
2)
 
1)
 
2)
 
1)
 
2)
 
1)
 
2)
 
Direct start ED=30 % 
(8xI
e
) / 0.4 s 
150 
1000  150 
1000  150 
1000  150 
1000  150 
1000  150 
1000 
ED=70 % (8xI
e
) / 0.4 s 
90 
500 
90 
500 
90 
500 
90 
500 
90 
500 
90 
500 
ED=30 % (8xI
e
) / 0.8 s 
75 
490 
75 
490 
75 
490 
75 
490 
75 
490 
75 
490 
ED=70 % (8xI
e
) / 0.8 s 
45 
250 
45 
250 
45 
250 
45 
250 
45 
250 
45 
250 
1) Duty cycle current rms value = 1.15 x I
e
 → motor protection 
2) Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.