Majestic Appliances ODGSR36A Manuale Utente

Pagina di 20
8
ODGSR Series Outdoor Gas Fireplace
20007114
Remote Wall Switch 
NOTE: Use an approved outdoor switch.
1. Thread wire through the low voltage wire access hole 
located on either side of unit. Do not cut wire or insu-
lation on metal edges. Ensure that wire is protected. 
Run the other end to a conveniently located wall 
receptacle box.  
2. Attach wire to switch and install switch into receptacle 
box. Attach cover plate to switch.
3. Connect wiring to gas valve. Refer to Figure 11.
CAUTION:  Do not wire millivolt remote wall 
switch for gas appliance to a 120v power 
supply. 
For lighting instructions, refer to Page 12.
NOTE: If glass doors are installed, the unit must be 
operated with the doors fully open. (Fig. 12) If the 
doors are not fully open, the thermodisk will auto-
matically turn the unit off. 
CAUTION: After the unit cools, the burner 
will automatically come on.
MD706-7
Glass Door Position
1/20/99
OPEN
Correct
Wrong
MD706-7
Fig. 12  Correct door position during operation.
Pilot
Thermodisk
On/Off 
Switch
Valve
HV105
Fig. 11  Remote switch wiring.
HV105
Generic Gas  Valve
9/22/99   djt
TPTH
TH
TP
Gas Line Installation
This appliance must be isolated from the gas supply 
piping system by closing its individual manual shut off 
valve during any pressure equal to or less than 1/2 psig 
(3.45 kPa).
The appliance and its individual shutoff valve must be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 1/2 psig (3.45 kPa).
If gas piping from the source to the appliance location 
has not been accomplished, install the required pipe. 
Consult local plumbing code to assure proper pipe size.
The gas pipeline can be brought in through the right 
side of the appliance. A knockout is provided to allow 
for the gas pipe installation and testing of any gas con-
nection.  
NOTE: The gas line connection can be made with 3/8" 
copper tubing approved for propane or natural gas, 1/2" 
rigid pipe or an approved flex connector, then reduced 
to 3/8" to the appliance. Because some municipalities 
have some additional local codes, it is always best to 
consult your local authority. 
U.S.: Consult the current National Fuel Gas Code, ANSI 
Z223.1/NFPA 54.
Canada: CSA - B149.1 installation code.
Test for leaks. Use a 50/50 solution of liquid soap and 
water to test for leaks at gas fittings and joints. Apply 
water/soap solution with brush only - do not over apply. 
NEVER 
test with an open flame.
The gas control is equipped with a captured screw type 
pressure test point, therefore it is not necessary to pro-
vide a 1/8" test point up stream of the control.
When using copper or flex connector use only approved 
fittings. Always provide a union so that gas line can 
be easily disconnected for burner or fan servicing.  
See gas specification for pressure details and ratings. 
NOTE: If flex connector is used, it must be kept inside 
of the appliance. (Fig. 10)
FP598
Fig. 10  Typical gas supply installation.
GF598
nvb GAS SUPPLY INSTALL
12/4/97
1/2" Gas Supply
1/2" x 3/8" Shut-off Valve
3/8" Nipple
3/8" Union
3/8" Nipple