  Example: Maximum horizontal length
  0 x 45° elbows  =  10’ (3 m)
  1 x 45° elbows  =  8¹⁄₂’ (2.6 m)
  2 x 45° elbows  =  7’ (2.1 m)
3.  A minimum of an 8’ vertical rise.
4.  Two sets of 45° elbows offsets within these vertical 
installations. From 0 to a maximum of 8’ (2.4 m) of 
vent pipe can be used between elbows. (Fig. 33)
5.  7DVCS must be used to support offsets. (Fig. 33) 
This application will require that you first determine 
the roof pitch and use the appropriate 7DVSKV (A, B 
or F). (Refer to Venting Components List, Page 27)
Vertical Through-the-Roof Installation
FP1021
Typical vertical 
through the roof
application
3/26/00   djt
Max. 
8’ 
(2.4 m)
45°
Max. 
8’ 
(2.4 m)
45°
50’
(15 m)
Typical 
Ceiling 
Support 
Application
Typical Roof 
Support Ap-
plication
FP1021
Typical Offset Installation
Fig. 33  Typical vertical roof applications.
1.  Locate your fireplace.
2.  Plumb to center of the (4”) flue collar from ceiling 
above and mark position.
3.  Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
4.  Proceed to plumb for additional openings through 
the roof. In all cases, the opening must provide a 
minimum of 1 inch clearance to the vent pipe, i.e., 
the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
5.  Place fireplace into position.
6.  Place firestop(s) #7DVFS or Attic Insulation Shield 
#7DVAIS into position and secure. (Fig. 34)
CFM100 
Firestop-Vertical
09/20/00
11"
11"
Joist
Joist
Firestop Spacer
Nails (4)
Upper Floor
Attic Insulation 
Shield
Ceiling 
Installation
CFM100
Fig. 34  Place firestop spacer(s) and secure.
7.  Install roof support (Fig. 35 & 36) and roof flashing 
making sure upper flange is below the shingles. (Fig. 
35)
8.  Install appropriate pipe sections until the venting is 
above the flashing. (Fig. 35)
If there is room above ceiling level, 
firestop spacer must be installed on both 
the bottom and the top side of the ceiling 
joists. If an attic is above ceiling level a 
7DVAIS (Attic Insulation Shield) must be 
installed. (Fig. 34)
The enlarged ends of the vent section 
always face downward. (Fig. 35)
TWL101a
Twist Lock Pipe
2/8/99   djt
3 #5 Sheet Metal 
Screws per Joint 
Storm Collar
TWL101a
Fig. 35  Roof flashing.
Sealant