Bradford-White Corp Copper Brute II Hydronic Boiler Manuale Utente

Pagina di 64
Page 36
 
B
RADFORD
 W
HITE
 C
ORP.
SECTION 6.
Operating Instructions
6.1  Sequence of Operation
A call for heat can be initiated either 
automatically (auto mode) under thermostatic control 
by the Copper Brute II temperature control, or by an 
external contact closure (manual mode).
In auto mode, the Copper Brute II burner will 
fire its stages of input to maintain a target temperature 
programmed into the temperature control. The 
controller can be programmed per 
Section 6.3.
In manual mode, an external control will control 
the Copper Brute II stages, as long as the Copper 
Brute II control is set to mode 6, and the auto/manual 
switch (located inside the control compartment) is set 
to manual.
The amber 
READY
 light on the front panel 
indicates that the control system is energized. Upon 
a call for heat, the green 
HEAT
 indicator on the front 
panel will light.
If the unit is pump-mounted, the pump will be 
energized. The pump terminals on the field-wiring 
terminals strip will energize a field pump that is 
properly interlocked with the Copper Brute II. The 
green 
PUMP
 indicator on the front panel will light.
Once the water flow switch makes, and if all of 
the safety interlocks are closed, the ignition module 
will energize the blower(s) for a 15-second pre-purge, 
followed by a 20-second period to allow the ignitor to 
heat.
Energizing the blower pressurizes the air box 
(which supplies air to the burners) and closes the 
normally-open contact(s) of the airflow pressure 
switch(es). This allows the ignition module to proceed 
with the ignition sequence.
The blocked flue pressure switch senses the 
pressure in the plenum. It will interrupt the airflow 
sensing circuit if this pressure exceeds a maximum 
value. If airflow is not proven, the ignition module  
will lockout.
The ignition module checks that the ignitor 
current has reached a minimum value and energizes 
the gas valve at the end of the ignitor heating period. 
The green 
STAGE 1
 indicator on the front panel will 
light, indicating that the stage 1 gas valve is open. 
After a 4-second trial for ignition, the ignitor 
switches off, and unless a flame is detected by the 
flame sensor, the gas valve will close and the ignition 
module will either attempt ignition again (up to three 
times) or will lockout (if the optional lockout ignition 
module is used).
If flame is sensed, the burner will continue to 
fire as long as there is a call for heat. In Auto mode, 
additional stages are delayed by a minimum of 60 
seconds (less prepurge and ignitor warm-up time) and 
once energized, must fire for at least 30 seconds. The 
request for additional stages is indicated on the control 
display, and the energizing of additional burner stages 
is indicated by front panel lights.
If there is a subsequent loss of flame signal, the 
burner will attempt re-ignition up to three times (only 
once if optional lockout ignition module is used.)
When the call for heat is satisfied, the gas 
valve(s) closes and the blower(s) continues to run 
for 30 seconds. The pump will continue to run for a 
minimum of 20 seconds and up to a programmable 
maximum of 10 minutes.
If a call for heat is prevented from being satisfied 
either by a safety interlock or due to an ignition 
lockout, the red 
SERVICE
 indicator on the front panel 
will light. To reset the standard ignition module, 
the reset button on the module must be pressed. 
Interrupting power to this module will not reset the 
lockout.
The Copper Brute II 1000–2000 models have 
two ignition modules that control different burners. If 
one module should fail for any reason, the remaining 
module can operate its burner(s) independently.
6.2  Filling the Boiler System
1.  Ensure the system is fully connected. Close all 
bleeding devices and open make-up water valve. 
Allow system to fill slowly.
2.  If make-up water pump is employed, adjust 
pressure switch on pumping system to provide 
a minimum of 12 psi (81.8 kPa) at the highest 
point in the heating loop.
3.  If a water pressure regulator is provided on the 
make-up water line, adjust the pressure regulator 
to provide at least 12 psi (81.8 kPa) at the highest 
point in the heating loop.
4.  Open bleeding devices on all radiation units 
at the high points in the piping throughout 
the system, unless automatic air bleeders are 
provided at such points.
5.  Run system circulating pump for a minimum of 
30 minutes with the boiler shut off.
6.  Open all strainers in the circulating system, 
check flow switch operation, and check for 
debris. If debris is present, clean out to ensure 
proper circulation.
7.  Recheck all air bleeders as described in 
Step 4.
8.  Check liquid level in expansion tank. With the 
system full of water and under normal operating 
pressure, the level of water in the expansion tank 
should not exceed ¼ of the total, with the balance 
filled with air.
9.  Start up boiler according to the procedure in this 
manual. Operate the entire system, including the 
pump, boiler, and radiation units for one (1) hour.
10.  Recheck the water level in the expansion tank. If 
the water level exceeds ¼ of the volume of the 
expansion tank, open the tank drain, and drain to 
that level.
11.  Shut down the entire system and vent all