BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS
3
63-4523—02
WIRING GUIDELINES 
Overview 
Honeywell uses EIA-485 as the physical layer between their devices and supervisory controllers 
For clarity we will use the term “Device” to represent any product with an active EIA-485 network connection, including Honeywell 
and non-Honeywell thermostats.
Table 2. Summary of Specifications for a Honeywell EIA-485 Network 
Cable Type 
Honeywell recommends the use of balanced 22-24 AWG twisted pair with a characteristic impedance of 100-130 ohms, 
capacitance of 30 pF/ft or lower. A braided shield is also recommended.
Impedance
A value based on the inherent conductance, resistance, capacitance and inductance that represent the impedance of an infinitely 
long cable. The nominal impedance of the cable should be between 100Ωand 120Ω. However using120Ω will result in a lighter 
load on the network.
Capacitance (pF/ft)
The amount of equivalent capacitive load of the cable, typically listed in a per foot basis. One of the factors limiting total cable 
length is the capacitive load. Systems with long lengths benefit from using low capacitance cable (i.e. 17pF/ft or lower).
Parameter
Details
Media
Twisted pair 22AWG-24 AWG, shielded recommended
Characteristic Impedance
100-130 ohms
Distributed capacitance
Less than 100 pF per meter (30 pF per foot)
Maximum length per segment
1200 meters (4000 feet) 
Polarity
Polarity sensitive
Multi-drop
Daisy-chain (no T connections)
Terminations
TB7600, TB7300, and/or TB7200 Series thermostats are 
installed at both ends of the MS/TP network: 
120 Ohms resistor 
should be installed at each end. To reduce issues with other 
BACnet devices we recommended keeping like devices on the 
same bus. TB7600, TB7300 and TB7200 Series thermostats can 
be installed on the same bus.
1.
A TB7600, TB7300, or TB7200 device is installed at one end of 
the MS/TP network and another device is installed at the other 
end:
Install an End-Of-Line resistor value that matches the other 
device's instructions regarding the End-Of-Line resistors
2.
Other devices are installed at both ends of the MS/TP net-
work:
Follow the other device’s instructions regarding the End-Of-Line 
resistors.
Maximum number of nodes per segment
64 (Honeywell devices only)
Maximum number of nodes per network
128
Baud rate
9600, 19200, 38400, 76800 (Auto detect)