Product Specifications
PHYSICAL DATA
MODEL NUMBER
AFPB24A1
AFPB24B1
AFPB36A1
AFPC48A1
AFPC48B1
AFPC60A1
AZFPC60B1
ELECTRIC DATA (208/230 VOLT, SINGLE PHASE, 60 Hz)
VOLTAGE
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
208 / 230
MINIMUM CIRCUIT AMPACITY MCA (AMPS)
15
15
15
15
15
15
15
MAXIMUM OVERCURRENT PROTECTIVE DEVICE - MOCP (AMPS)
15
15
15
15
15
15
15
BLOWER 
FAN MOTOR TYPE
PSC
HP
1/6
1/6
1/3
1/2
1/2
3/4
3/4
BLOWER DIMENSIONS
9 x 7
9 x 7
9 x 10 
9 x 8
9 x 8
10 x 9 
10 x 9 
COIL DATA
TYPE
A-COIL
COIL FACE AREA (ft
2
)
4
4
4
5.8
5.8
5.8
5.8
O.D.
3/8"
ROWS / FPI
2 - 14
3 - 14
3 - 14
3 - 12
4 - 12
3 - 12
4 - 12
REFRIGERANT LINE CONNECTION
LIQUID LINE CONNECTION SIZE (IN. OD)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
SUCTION LINE CONNECTION SIZE (IN. OD)
3/4
7/8
7/8
7/8
7/8
7/8
7/8
FILTER DATA
RECOMMENDED FILTER SIZE (H X W X D) (in)
(FILTER NOT SUPPLIED)
16 x 20 x 1
16 x 20 x 1
16 x 20 x 1
20 x 25 x 1
20 x 25 x 1
20 x 25 x 1
20 x 25 x 1
2
Specifications subject to change without notice.
Clearance to Combustible Material
Clearances from the air handler to the combustibles are zero inches from all sides, top, and bottom; one inch from discharge 