LST NNU5-1 Dépliant

Pagina di 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
NNU5-1_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
Specifi cations
The  Network  Redundant  Alarm  Converter  NNU5-1  is 
required  in  the  network  fi re  detection  control  panel 
 BCnet216  for  the  alarm  transmission  according  to 
ÖNORM F 3000. It has to be installed in every sectional 
control panel that is connected to the transmitting de-
vice to the fi re brigade. The componentry guarantees 
the alarm transmission to a transmitting device despite 
multiple line failures in the GSSnet.
•   Monitors up to 126 members of 
a Fire Detection Control Panel 
BCnet216
•   Circular redundant alarm line 
monitored for wire breakage
•   Meets redundancy requirements of 
ÖNORM F 3000
•   Easy installation in fi re detection 
control panel Series BC216
Current consumption at 24V 
typ. 4mA
BCnet redundant alarm line 
2-core circular line
Line resistance  
max. 1kΩ
Ambient temperature 
-5°C to +50°C
Dimensions L × W × H 
75 × 40 × 15 (mm)
Weight 
40g
Part No. 
214031
Order name 
Network Redundant Alarm Converter NNU5-1