Unusually tight construction is defined as 
construction where:
a.  walls and ceilings exposed to the out-
side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6 x 10
-11
 kg per pa-sec-m
2
) or 
less with openings gasketed or sealed 
and
b.  weather stripping has been added on 
openable windows and doors and
c.  caulking  or  sealants  are  applied  to 
areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical and gas lines 
and at other openings.
If your home meets all of the three criteria 
above, you must provide additional fresh air. 
See Ventilation Air From Outdoors
, page 8. 
If your home does not meet all of the three 
criteria  above,  proceed  to  Determining 
Fresh-Air Flow For Fireplace Location
.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 
54 defines a confined space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per hour 
(4.8 m
3
 per kw) of the aggregate input rating of all 
appliances installed in that space and an unconfined 
space as a space whose volume is not less than 50 
cubic feet per 1,000 Btu per hour (4.8 m
3
 per kw) of 
the aggregate input rating of all appliances installed 
in that space. Rooms communicating directly with 
the space in which the appliances are installed*, 
through openings not furnished with doors, are 
considered a part of the unconfined space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation grills 
between them.
DETERMINING FRESH-AIR FLOW 
FOR FIREPLACE LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have a 
confined or unconfined space.
Space:
 Includes the room in which you will install 
heater plus any adjoining rooms with doorless 
passageways or ventilation grills between the 
rooms.
AIR FOR COMbUSTION 
AND VENTILATION
Continued
1.  Determine the volume of the space (length x 
width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: 
Space size 20 ft. (length) x 16 ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)
 
If additional ventilation to adjoining room is 
supplied with grills or openings, add the volume 
of these rooms to the total volume of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
 __________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example:
 2560 cu. ft. (volume of space) x 20 = 
51,200 (maximum Btu/Hr the space can support)
3.  Add the Btu/Hr of all fuel burning appliances in 
the space.
 
Vent-free heater 
  ____________ Btu/Hr
 
Gas water heater* 
  ____________ Btu/Hr
 
Gas furnace 
  ____________ Btu/Hr
 
Vented gas heater 
  ____________ Btu/Hr
 
Gas fireplace logs 
  ____________ Btu/Hr
 
Other gas appliances*  + ___________ Btu/Hr
 
Total 
= ___________ Btu/Hr
 
* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors 
and vents to the outdoors.
 
Example:
 
Gas water heater 
  ____________ Btu/Hr
 
Vent-free heater 
+ ___________ Btu/Hr
 
Total 
= ___________ Btu/Hr
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
 _________Btu/Hr (maximum the space can support)
 
 _________Btu/Hr (actual amount of Btu/Hr used)
 
Example:
  51,200 Btu/Hr (maximum the space 
can support)
 
 
56,000  Btu/Hr  (actual  amount  of 
Btu/Hr used)
The space in the above example is a confined space 
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must provide 
additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined 
space, remove door to adjoining room or add 
ventilation grills between rooms. See Ventilation 
Air From Inside Building, page 8.
B.  Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors, page 8.
C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 
size makes room unconfined.
30,000
26,000
56,000