DSKS333EC 
GE Spacemaker
® 
Stationary Dryer
Dimensions and Installation Information (in inches) 
Best performance
Domestic  
dryer models
Maximum length of 4"
dia. 
rigid metal duct
Number
of
90°
turns
Exhaust hood type
A
4" 
opening
B
2-1/2" 
opening
DSKS433EB
DSKS333EC
DSKP333EC
WSM2780H
3
46 ft.
38 ft.
31 ft.
24 ft.
37 ft.
30 ft.
22 ft.
15 ft.
WSM2700H
3
56 ft.
46 ft.
34 ft.
32 ft.
42 ft.
36 ft.
28 ft.
18 ft.
WSM2420D*
WSM2480D*
2
43 ft.
33 ft.
23 ft.
36 ft.
26 ft.
16 ft.
A
4
B
2-1/2
*Foil ducting not allowed
A
For complete information, see installation instructions packed with your dryer.
Ducting Materials:
 
For best performance, this dryer should be vented with 4" diameter all rigid metal 
exhaust duct. If rigid metal duct cannot be used, then UL-listed flexible metal 
(semi-rigid) ducting can be used (Kit WX08X10077). In special installations, it may be 
necessary to connect the dryer to the house vent using a flexible metal (foil-type) 
duct. A UL-listed flexible metal (foil-type) duct may be used ONLY in installations 
where rigid metal or flexible metal (semi-rigid) ducting cannot be used AND where a 
4” diameter can be maintained throughout the entire length of the transition duct. 
Please see installation instruction packed with your dryer for complete instructions 
when using flexible metal (foil type) ducting. 
Exhaust Length Calculation: 
1.  Determine the number of 90° turns needed for your installation. If you exhaust to 
the side or bottom of dryer, add one turn.
2.  The maximum length of 4' rigid (aluminum or galvanized) duct which can be 
tolerated is shown in the table. 
   A turn of 45° or less may be ignored. Two 45° turns within the duct length should 
be treated as a 90° elbow. A turn over 45° should be treated as a 90° elbow.
Dryers 
must be exhausted to the outside.
Caution: For personal safety do not terminate exhaust into a chimney, under any 
enclosed house floor (crawl space), or into an attic, since the accumulated lint could 
create a fire hazard or moisture could cause damage. Never terminate the exhaust 
into a common duct or plenum with a kitchen exhaust, since the combination of lint 
and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts, 
bird nesting, etc. The wall cap must also be located at least 12" above the ground or 
any other obstruction with the opening pointed down.