REFRIGERATION DATA
Note: This data is based on store temperature and
humidity that does not exceed 75F and 55% R.H.
humidity that does not exceed 75F and 55% R.H.
Discharge Air (F)
35
Evaporator (F)
25
Note: Not recommended to control temp by regulating
coil temp allow t-stat to cycle and control temp.
coil temp allow t-stat to cycle and control temp.
½ Case
Btu/hr/total*
Parallel
Parallel
10,500
Conventional 12,075
Full Case
Btu/hr/total*
Parallel
Parallel
21,000
Conventional 24,150
*For all refrigeration equipment other than Hussmann,
use conventional Btu values.
use conventional Btu values.
DEFROST DATA
Frequency Hrs
4
OFFTIME
Temp Term °F
Temp Term °F
54
Failsafe Minutes
24
ELECTRIC or GAS Not Recommended
PHYSICAL DATA
Merchandiser Drip Pipe (in.)
1 ½*
Merchandiser Liquid Line (in.)
3/8*
Merchandiser Suction Line (in.)
5/8*
Estimated Charge (lb)***
4ft 1.2
5ft 1.5
6ft 1.8
5ft 1.5
6ft 1.8
*Dependent on case length and refrigerant type.
*** This is an average for all refrigerants types. Actual
refrigerant charge may vary by approximately half a
pound.
refrigerant charge may vary by approximately half a
pound.
GLYCOL REQUIREMENTS
GPM PSI
NA
NA
NA
NA
NA
NA
CUL Listed