Honeywell B Guida All'Installazione
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
69-1175EF—05 K.K. Rev. 02-10
Printed in U.S.A
© 2010 Honeywell International Inc.
69-1175EF—05 K.K. Rev. 02-10
Printed in U.S.A
Template (entire sheet), Top of Humidifier
Template (entire sheet)
Te
mplate (e
nt
ir
e sh
ee
t)
Te
mp
late (entire sh
late (entire sh
eet)
Fig. 5. Typical wiring diagram for humidifier using fan control to
cycle blower motor fan and humidifier simultaneously.
Fig. 6. Typical wiring diagram of current sensing relay with
humidifier.
Fig. 7. Typical wiring diagram of sail switch with humidifier.
Plumbing Saddle Valve
Hot or cold water, either hard or softened, can be used in the
humidifier.
1. Use the self-piercing saddle valve (included) to tap into the
water supply line at an appropriate location.
CAUTION
Equipment Hazard.
Can cause equipment damage.
• Do not use any line connected to an air conditioner.
IMPORTANT
• The saddle valve is not designed to regulate water flow; the
valve is either open or closed.
• To prevent debris from clogging the solenoid in-line filter, be
sure to install the saddle valve handle pointing toward the
ceiling.
NOTE: Lightly clean the copper tubing ends with fine sandpaper
before making any connections.
2. Use 1/4 in. O.D. copper tubing and connect the saddle valve to
the inlet side of the solenoid valve.
a. Place the brass compression nut over the copper tubing.
b. Slide the brass ferrule over the tubing.
NOTE: Do not over-tighten the compression nut. Moderate
tightness prevents leaking.
c. Insert the tubing into the solenoid valve fitting and support
the valve while tightening the compression nut.
NOTE: Slope hose downward for correct drainage.
3. Connect a 1/2 in. hose to the humidifier drain fitting and run it to
a suitable drain.
CHECKOUT
1. Open the saddle valve.
NOTE: The furnace blower must be operating for the
humidifier to work.
2. Set the thermostat setpoint 10°F (6°C) above the room
temperature.
3. Set the humidistat to a high humidity setting, or place the
humidistat in the test position.
4. Observe the water running out of the drain line to be sure the
humidifier is working correctly.
5. Check for leaks.
6. Reset the thermostat and humidistat to comfortable settings.
HUMIDIFIER
MECHANICAL
HUMIDISTAT
120 VAC
TO BLOWER
MOTOR
IGNITION BOX
M12686A
YELLOW WIRES
1
1
2
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24V WIRING.
CURRENT
SENSING
RELAY
HUMIDIFIER
120 VAC
BLOWER
MOTOR
C
LO
HI
M12684A
YELLOW WIRES
1
1
2
2
POWER SUPPLY.
PROVIDE DISCONNECT
MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
24V WIRING.
MECHANICAL
HUMIDISTAT
SAIL
SWITCH
HUMIDIFIER
120 VAC
M12685A
YELLOW WIRES
1
1
2
2
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
24V WIRING.
MECHANICAL
HUMIDISTAT
69-1175E_C.fm Page 2 Thursday, February 11, 2010 4:52 PM