Honeywell Electrode Humidifier [with HumidiPRO™ H6062 Digital Humidity Control (HM700A1000)] Manuale Proprietario

Pagina di 12
HM700A1000 Electrode Steam Humidifier
QUICK INSTALLATION GUIDE
TOOLS & SUPPLIES NEEDED
•  Screwdriver
•  Shut-off water valve
•  Wrench
•  Water line (LDPE or Copper)
•  Pliers
MOUNTING
Requirements
•  Wall mount, minimum of 24 inches above floor.
•  Unit must be level.
•  Location must have ambient temp between 41° and 104° F.
•  Location must have relative humidity of 5-95%.
•  Allow 36 inch front clearance.
24” (61 cm) minimum
41˚ - 104˚ F
(5˚ - 40˚ C)
5-95%
As close as possible to
steam distributor.
M36301
Mounting Process
1.  Preparation: use #8 screws at least 2” (5 cm) in length. Mount on 2x4 studs 
(or stronger) vertical surface.
2.  Install the rst screw at least 43.5 in. above the oor. Leave 1/4” (6 mm) of the 
shaft exposed for hanging the unit.
1/4” (6 mm)
43.5” minimum above floor
M36302
3.  Hang unit from top screw using the key-hole on back and ensure it is level.
+
M36303
4.  Secure unit with second screw driven through hole at bottom.
M36304
PLUMBING
Supply Requirements
•  Use potable water;
•  DO NOT use reverse osmosis or de-ionized water.
•  Pressure: 30-100 PSI;
•  Conductivity: 125-1250 microsiemens;
•  Temperature: 34-68° F (1-20° C).
Supply Plumbing
Connect to 1/2” OD Copper or 
plastic supply line, 4 feet (or 
less) from humidifier.
Use 1/4” compression fitting 
(included) to connect water 
supply line to unit (LDPE plastic 
or copper).
Always install a water shut-off valve and 
coupler to facilitate future servicing.
M36305
Drain Line Installation Process
M36305
M36306
1.  Attach drain hose elbow/reducer to drain 
canal using supplied hose clamp.
2.  Attach drain hose to reducer using 
supplied spring clamp.
3.  Route drain line to a oor drain and ensure 
it is sloped to provide easy draining.
33-00162EFS-03