ST16 Hardware Platform Overview   
▀  Power Filter Units 
 
▄  Cisco ASR 5000 Series Product Overview 
OL-22937-01   
Power Filter Units 
Located at the bottom rear of the chassis are slots for two Power Filter Unit (PFU) assemblies. Each PFU provides DC 
power from the Central Office (CO) battery sub-system to the chassis and its associated cards. Each load-sharing PFU 
operates independently of the other to ensure maximum power feed redundancy. The maximum input operating voltage 
range of the PFU is -40 VDC to -60 VDC; the nominal rage is -48 VDC to -60 VDC. 
Important:
  In the event that the CO has AC power only, a separate rack mount AC to DC converter is required. 
There are two versions of the PFU. The versions are differentiated by the current rating of the circuit breakers: 125 amp 
and 165 amp. Older versions of the ST16 chassis use the 125A PFU. Newer versions of the ST16 chassis use the 165A 
PFU. 
Caution:
  125A and 165A PFUs are not interchangeable. Both PFUs installed in chassis must be of 
the same type. 
The following drawing shows the PFU and its connectors. Refer to the Cabling the Power Filter Units chapter for 
information on installing and cabling the PF. 
Figure 16.  Power Filter Unit 
../../../GRAPHICS/Production/ST-series_Hardware/PFUv2.wmf 
Table 7. Power Filter Unit Component Descriptions 
Item
 
Description
 
1
 
Plastic terminal cover
 
2
 
VDC (-48 VDC input terminals)
 
3
 
RTN (voltage return terminals)
 
4
 
Power filter unit handle
 
5
 
Circuit breaker (On/Off) rated at either 125A or 165A depending on chassis requirements
 
6
 
Power LED (See Hardware Installation Guide for details.)