  Troubleshooting 
Detecting Faulty Hardware  ▀   
 
ASR 5000 System Administration Guide, StarOS Release 16  ▄  
 
   
199 
Checking the LED on the PFU 
Each PFU has a single status LED labeled POWER.  
This LED should be green for normal operating conditions. 
Figure 11.  PFU LED Location 
 
The possible states for this LED are described in the following table. If the LED is not green, use the troubleshooting 
information below to diagnose the problem. 
Table 13. 
PFU POWER LED States 
Color
 
Description
 
Troubleshooting
 
Green
 
PFU powered with no 
errors detected
 
None needed. 
None
 
PFU is not receiving 
power
 
Verify that the power switch is in the ON position.
 
Verify that the RTN and -VDC lugs are attached properly.
 
Verify that the ground lug is attached properly. Verify that the power source is on and is 
supplying the correct voltage and sufficient current.
 
Check the cables from the power source to the rack for continuity.
 
If a power distribution panel (PDP) is installed between the power distribution frame (PDF) 
and the chassis, verify that the circuit breakers are set to ON.
 
If a PDP is installed between the PDF and the chassis, check the cables from the PDP to the 
chassis for continuity.
 
If all of the above suggestions have been verified, then it is likely that the PFU is not 
functional. Please contact your service representative.