AEG 1.04 Manuale Utente
11
176 VAC – 264 VAC ±3%
(Bypass)
Frequency
50 Hz / 60 Hz
(Automatic detection)
(Automatic detection)
Frequency tolerance range
±4 Hz
Current consumption at full load (max.)
PROTECT 1.M (system)
PROTECT 1.M (system)
44 A (3ph~) or 132 A (1ph~) / 155
A (Bypass)
A (Bypass)
PROTECT 1.040 (module)
7.3 A (3ph~) or 22 A (1ph~)
System disturbance factor
λ ≥ 0.98
UPS output
Nominal voltage output
220 / 230 / 240 Vac ±2%
(configuration via "CompuWatch"
software)
(configuration via "CompuWatch"
software)
Nominal frequency
50 Hz / 60 Hz ±0.2 Hz (dependent
on mains frequency)
on mains frequency)
Type of voltage
Sine, distortion
< 3% THD (linear load)
< 6% THD (non-linear load)
Crest factor
3:1
Overload behaviour
Up to 105% continuous;
with mains supply
> 105% – < 130% for 30s
130% for 2
s
Following this, automatic,
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min. if overload
continues to be present (switch
back if overload decreases = load
< 90%)
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min. if overload
continues to be present (switch
back if overload decreases = load
< 90%)
Overload behaviour with
Up to 105% continuous;
battery operation
> 105% – < 130% for 30s
130% for 2
s
Short-circuit behaviour
3 x I
N
for 100 ms