21 
4.2 
Transport to Installation Site 
The PROTECT 1.M is equipped with transport rolls for easy 
transport to the intended installation site. It is recommended to 
install the UPS where: 
♦  The connection work can be conveniently carried out; 
♦  There is enough space for proper operation and, if 
necessary, for periodic and extraordinary maintenance 
work; in this regard, the connection cables should be 
long enough to move the UPS (to open the UPS if 
necessary) without having to switch it off. 
♦  The UPS is protected against external atmospheric 
influences; 
♦  The humidity and the ambient temperature are within the 
limits; 
♦  The fire protection standards are observed. 
The battery service life strongly depends on the ambient 
temperature. Ambient temperatures between +15 °C and +25 
°C are optimum. 
 
Attention!
 
Only transport the PROTECT 1.M in an upright 
position
!  Never tilt or cant it; avoid displacing 
the centre of gravity! 
Make sure that no magnetic storage media are stored and/or 
operated close to PROTECT 1.M.