UPS operations  27 
To place the UPS in Operate mode, press the On button. The Utility LED turns solid green, indicating that 
power is available at the UPS output receptacles. The UPS acknowledges compliance with a short beep. 
  NOTE:   
  If the UPS is using battery power (no utility power is present and the Utility LED is red), press and hold 
the On button until the audible alarm sounds. 
  If the UPS is off (no LEDs are illuminated), press the On button to start the UPS on battery power. 
For the location of buttons, see "UPS front panel controls (on page 
For the location of LEDs, see "UPS front panel LED indicators (on page 
 
Configure mode 
In Configure mode: 
 
Power is available at the UPS receptacles. 
 
The UPS charges the batteries as necessary. 
 
The UPS configuration can be updated. 
The UPS can be placed in Configure mode while in Operate mode (on page 
or Standby mode (on 
To place the UPS in Configure mode: 
1.
 
Remove the front bezel ("
2.
 
Press and hold the Configure button until the front panel LEDs flash in unison and the Configure 
Mode On LED illuminates solid green. 
For the location of buttons, see "UPS front panel controls (on page 
For the location of LEDs, see "UPS front panel LED indicators (on page 
 
Auto-Bypass mode 
The UPS automatically enters Auto-Bypass mode when either of the following conditions occurs: 
 
The power from the UPS reaches a percentage greater than 110 percent for more than 10 cycles or 
between 103 percent and 110 percent for more than 2 minutes. 
 
The UPS electronics module fails or is removed. 
 
Configuring the UPS 
In Configure mode, the LED front panel display changes function to enable modification of the UPS 
parameters. Each LED is associated with a different parameter. 
     
Available settings 
Parameter  
Associated LED 
Explanation (when LED is illuminated) 
Nominal Voltage 
Setting 
200/208 Nom 
General Alarm 
(red) 
Nominal utility voltage level is set to 
200/208 VAC (factory default for 326529-
D71) 
 
220 Nom 
On Battery (red)  Nominal utility voltage level is set to 220 
VAC 
 
230 Nom 
Battery Fault 
(red) 
Nominal utility voltage level is set to 230 
VAC (factory default for 326529-B31) 
 
240 Nom 
Site Wiring Fault 
(red) 
Nominal utility voltage level is set to 240 
VAC