The increasing power of new high-performance processor technology requires increased cooling
efficiency for rack-mounted servers. The 10000 G2 Series Racks provide enhanced airflow for maximum
cooling, allowing these racks to be fully loaded with servers using the latest processors.
CAUTION:
CAUTION:
CAUTION:
CAUTION: If a third-party rack is used, observe the following additional requirements to ensure
adequate airflow and to prevent damage to the equipment:
Front and rear doors: If your 42U server rack includes closing front and rear doors, you must
allow 830 square inches (5,350 sq cm) of hole evenly distributed from top to bottom to permit
adequate airflow (equivalent to the required 64 percent open area for ventilation).
Side: The clearance between the installed rack component and the side panels of the rack must be
a minimum of 2.75 inches (7 cm).
CAUTION:
CAUTION:
CAUTION:
CAUTION: Always use blanking panels to fill all remaining empty front panel U-spaces in the rack. This
arrangement ensures proper airflow. Using a rack without blanking panels results in improper cooling
that can lead to thermal damage.
NOTE:
NOTE:
NOTE:
NOTE: For additional information, refer to the Setup and Installation Guide or the Documentation CD
provided with the server, or to the server documentation located in the Support section at the following
URL: 
.
Rack Kit
Rack Kit
Rack Kit
Rack Kit
Quick deploy rail system provides tool-free support for racks with square or round mounting holes
(including Compaq/HP 7000, 9000, 10000 G2 and HP series), with an adjustment range of 24" - 36".
The ambidextrous cable management arm can be mounted on either the left or right side for improved
cable management.
NOTE: 
NOTE: 
NOTE: 
NOTE: High Airflow Inserts (High Air Flow Rack Door Insert for the 7142 Rack (single) - PN: 327281-
B21; or High Air Flow Rack Door Insert for the 7142 Rack (6-pack) - PN: 327281-B22) are required to
support the HP ProLiant DL380 in 7000 series racks. The DL380 Cable Management Arm is not
supported on 7000 series racks.
NOTE:
NOTE:
NOTE:
NOTE: Cable management arm must be removed to access hot-plug power supplies when the cable
management arm is mounted on the right.
Telco Rack Support
Telco Rack Support
Telco Rack Support
Telco Rack Support
Support for all 2-post Telco racks requires the use of the standard rack kit and an additional option kit