Toshiba G3 TOSVERT-130 Manuale Utente

Pagina di 62
 
 19
Indicators 
1 green LED is provided to indicate when the interface has achieved the 
DATA_EXCHANGE state with the network master.  This serves as a convenient 
indicator that the master and drive are configured properly and are exchanging data. 
 
 
Isolation 
The network interface portion of the Profibus-DP board is fully optically-isolated for 
optimal noise-immunity characteristics. 
 
 
Network Connector 
The network interface is a standard DB9 connector with the following signals 
provided: 
 
Pin 
Number Function In/Out 
Profibus network “B” (positive) data line 
In/out 
RTS signal – direction control for fiber optic network 
interface 
Out 
DGND – power supply ground internally connected to the 
interface board’s isolated ground  
VP – power supply +5v internally connected to the 
interface board’s isolated P5. 
Profibus network “A” (negative) data line 
In/out 
1, 2, 7, 9 
No connection 
 
In addition to the above signals, the metallic housing of the DB9 connector is 
connected to the shield section of the interface board.  The shield section contains a 
plated connection point where a ground wire can be attached to connect the network 
cable shield to ground.  Refer to section 3 of this document for more information 
related to grounding. 
 
 
Input/Output Data 
The interface’s cyclic data sizes are fixed at 8 bytes of output (control) data 
configured as 4 words, and 16 bytes of input (status) data configured as 7 words and 
2 bytes.  For detailed explanations of the format and usage of this data, refer to 