2-4.  Outer Dimensions of Outdoor Unit
unit: mm
608
85
790
3
10
2
8
5
33
6
70
569
15
15
8
70
46
122
70
142
A
A
(Outer diameter ø6.35)
(Outer diameter ø9.52)
Service valve on 
wide tube side
Service valve on 
narrow tube side
Fig. 6a
2-5.  
Diagram of Outdoor Unit Installation
Never install only a single indoor unit.
Be sure to connect indoor and outdoor units only in 
combinations that are listed in the catalog or in the 
combination table that was provided with the outdoor unit.
(Use caution. Connecting any other model may result in 
operation failure and malfunction.)
The dimensions indicated by 
 in the figure below are 
spaces that are required in order to maintain 
performance. Install in a location where the dimensions 
indicated by 
 are ensured, and where 2 or more faces 
of the unit are unobstructed. In principle, the top direction 
should be unobstructed.
Indoor unit B
Indoor unit A
Service space
Power breaker
Ground
wire
(not 
provided) 
Ensure 15cm
of space if a
drain hose is to
be used.   
Base (not provided)
(concrete or similar material)
Fasten with anchor bolts 
(not provided) 
(3/8" or M10, 4 locations)
A
B
Access panel  C
Ov
er 25cm
Ov
er 10cm
Ov
er 5cm
Ov
er 40cm
Fig. 6b